| Parameter | Wert |
|---|---|
| Artikel | Specifications |
| Kabel | 0.15 mm23-core oil, heat and cold resistant cabtyre cable, 1 m3.281 ftlong |
| Ausgabe | PNP open-collector transistor- Maximum source current: 100 mA- Applied voltage: 30 V DC or less(between output and +V)- Residual voltage: 2 V or less (at 100 mA source current) |
| Details | PNP output |
| Produkt | Rectangular-shaped Inductive Proximity Sensor |
| Material | Enclosure: PBTIndicator part: Polyester |
| Hysterese | 20 % or less of operation distance(with standard sensing object) |
| Nettogewicht | 20 g approx. |
| Schutz | IP68 (IEC), IP68g (JEM)(Note) Panasonic Electric Works SUNX's IP68 test method1. Immerse at 0 m below 0 ℃+32 ℉water surface and leave for 30 min. Then, immerse at 0 m below +70 ℃+158 ℉water surface and leave for 30 min.2. Regard the heat shock test in 1 as one cycle and perform 20 cycles.3. Leave in water at a depth of 1 m3.281 ftin water for 500 hours.4. After tests 1 to 3, insulation resistance, voltage withstandability, current consumption, and sensing ranges must meet the standard values.(Note) If using the sensor in an environment where cutting oil droplets splatter, the sensor may be deteriorated due to added substances in the oil. |
| Teilenummer | GX-H12B-P |
| Produktname | Rectangular-shaped Inductive Proximity Sensor GX-F/H |
| Wiederholbarkeit | Along sensing axis, perpendicular to sensing axis: 0.04 mm0.002 inor less |
| Produktnummer | GX-H12B-P |
| Versorgungsspannung | 12 to 24 V DC +10/-15 % Ripple P-P 10 % or less |
| Kabelverlängerung | Extension up to total 100 m328.084 ftis possible with 0.3 mm2, or more, cable. |
| Umgebungsfeuchtigkeit | 45 to 85 % RH, Storage: 35 to 95 % RH |
| Stoßfestigkeit | 10,000 m/s2acceleration (1,000 G approx.) in X, Y and Z directions three times each |
| Umgebungstemperatur | -25 to +70 ℃-13 to +158 ℉, Storage: - 40 to +85 ℃- 40 to +185 ※ |
| Aktueller Verbrauch | 15 mA or less |
| Betriebsanzeige | Orange LED(lights up when the output is ON) |
| Stabiler Erfassungsbereich | 0 to 3.3 mm0 to 0.130 in(Note) The stable sensing range stands for the sensing range for which the sensor can stably detect the standard sensing object even if there is an ambient temperature drift and/or supply voltage fluctuation. |
| Vibrationsfestigkeit | 10 to 500 Hz frequency, 3 mm0.118 indouble amplitude (Max. 20 G) in X, Y and Z directions for two hours each |
| Isolationswiderstand | 50 MΩ , or more, with 500 V DC megger between all supply terminals connected together and enclosure |
| Maximale Betriebsdistanz | 4.0 mm0.158 inplus or minus 8 %(Note) The maximum operation distance stands for the maximum distance for which the sensor can detect the standard sensing object. |
| Maximale Ansprechfrequenz | 500 Hz |
| Ausgabe: Ausgabeoperation | Normally closed |
| Standard-Erfassungsobjekt | Iron sheet 20 × 20 × t 1 mm0.787 × 0.787 × t 0.039 in |
| Spannungsfestigkeit | 1,000 V AC for one min. between all supply terminals connected together and enclosure |
| Ausgabe: Nutzungskategorie | DC-12 or DC-13 |
| Anwendbare Vorschriften und Zertifizierungen | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) |
| Variation des Erfassungsbereichs: Spannungscharakteristik | Within plus or minus 2 % for +10/-15 % fluctuation of the supply voltage |
| Variation des Erfassungsbereichs: Temperatureigenschaften | Over ambient temperature range -25 to +70 ℃ -13 to +158degrees Fahrenheit: Within plus or minus 8 % of sensing range at +23 ℃ +73 ℉ |
Technische Spezifikationen und Leistungsdaten
Installations- und Betriebsanleitung