| Parameter | Wert |
|---|---|
| EAN | 4048879080675 |
| Wellen | max. 20 mV eff/rms |
| Spikes | max. 80 mV ss/pp |
| eClass | 27049002 |
| Art.-Nr.: | 85061 |
| Frequenz | 50...60 Hz |
| Standards | EN 60950-1, EN 61204-3, EN 55022 B, EN 61000-3-2 |
| Effizienz | 83% (115 V AC); 87% (230 V AC) |
| LED-Anzeige | LED (green) for output voltage |
| Eingangsstrom | 1.4 A (100 V AC); 0.6 A (230 V AC) |
| Eingangsspannung | 90...265 V AC |
| Ausgangsstrom | 5 A (+60 °C); 6 A (+40 °C, 110...265 V AC) |
| Ausgangsspannung | 24 V DC (SELV), ±1%; 24...28 V adjustable |
| Verpackungseinheit | 1 |
| Montageart | DIN-rail mountable TH35 (EN 60715) |
| Einheitenschutz | Short-circuit and overload protected |
| Relative Luftfeuchtigkeit | 5...95%, no condensation |
| Temperaturbereich | 0...+60 °C (storage temperature -25...+85 °C) |
| Ursprungsland | CZ |
| Alternativprodukt: | Product ComparisonINPUT: 90...265 V ACOUTPUT: 24...28 V DCCurrent: 5 AInputInput voltage90...265 V ACInput current1.4 A (100 V AC); 0.6 A (230 V AC)Inrush current after 1 msmax. 25 APrimary fusing externalmax. 10 AFrequency50...60 HzGeneral dataStandardsEN 60950-1, EN 61204-3, EN 55022 B, EN 61000-3-2Mounting methodDIN-rail mountable TH35 (EN 60715)Efficiency83% (115 V AC); 87% (230 V AC)Relative humidity5...95%, no condensationDimensions H × W × D115×54×151 mmTemperature range0...+60 °C (storage temperature -25...+85 °C)OutputOutput voltage24 V DC (SELV), ±1%; 24...28 V adjustableOutput current5 A (+60 °C); 6 A (+40 °C, 110...265 V AC)Mains failure bridging timemin. 18 ms (230 V AC)Ripplemax. 20 mV eff/rmsSpikesmax. 80 mV ss/ppUnit protectionShort-circuit and overload protectedLED displayLED (green) for output voltageSelectable switch-off modefront sided plug link (automatic re-start or definite shut-off)Parallel usage/serial usagemax. 5 units/max. 2 unitsCommercial datacountry of originCZcustoms tariff number85044090EAN4048879080675eClass27049002Packaging unit1 |
| Zolltarifnummer | 85044090 |
| Abmessungen (H × B × T) | 115×54×151 mm |
| Primäre externe Sicherung | max. 10 A |
| Einschaltstrom nach 1 ms | max. 25 A |
| Wählbarer Abschaltmodus | front sided plug link (automatic re-start or definite shut-off) |
| Überbrückungszeit bei Netzausfall | min. 18 ms (230 V AC) |
| Parallele Nutzung/Serielle Nutzung | max. 5 units/max. 2 units |
Technische Spezifikationen und Leistungsdaten
Installations- und Betriebsanleitung