| Parameter | Wert |
|---|---|
| MTBF | 430 000 h |
| Wellen | max. 10 mV eff/rms |
| Spikes | max. 150 mV ss/pp |
| Frequenz | 50...60 Hz |
| Standards | IEC 61010-2-201, EN 61204-3, EN 55022 B, EN 61000-3-2 |
| Verbindung | M12 (female) 5-pole, L-coded |
| Effizienz | 91.6% (115 V AC); 92.8% (230 V AC) |
| Schutz | IP67 |
| LED-Anzeige | LED (green): OK; LED (red): overload, overheating or short-circuit |
| Leistungsfaktor | 0.88 (230 V AC) |
| Eingangsstrom | 1.2 A (240 V AC) |
| Eingangsspannung | 90...265 V AC/90...265 V DC |
| Ausgangsstrom | max. 8 A (per channel), max. 10 A (total) |
| Ausgangsspannung | 24 V DC (PELV), ±1%; 24...28 V adjustable |
| Montageart | 6 hole screw mounting |
| Anzahl der Kanäle | 2× MICO (Over current protection device) |
| Einheitenschutz | Short-circuit, overload and temperature |
| Relative Luftfeuchtigkeit | 4...100% |
| Temperaturbereich | -25...+50 °C, ...+80 °C derating (storage temperature -25...+85 °C) |
| Abmessungen H×B×T | 216×110×53 mm |
| Eingangssicherung (intern) | 6.3 A (T) |
| Einschaltstrom nach 1 ms | max. 5.9 A (230 V AC) |
| Überbrückungszeit bei Netzausfall | min. 20 ms (230 V AC) |
| Parallele Nutzung/Serielle Nutzung | no |
| Produktartikelnummer des Herstellers | 85688 |
Technische Spezifikationen und Leistungsdaten