| Parameter | Wert |
|---|---|
| -40 °F ... 158 °F (>131°F derating) | |
| MTTF | 778 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| Tiefe | 114.5 mm |
| IECEx | Ex nA nC IIC T4 Gc |
| Reichweite | ± 5 km (The range may be considerably above or below that stated, and depends on the environment, antenna technology, and the product used) |
| Schock | 16g, 11 ms |
| Breite | 17.5 mm |
| Höhe | 2000 m |
| Sicherheit | 128-bit data encryption |
| Datenrate | 16 kbps (adjustable) |
| Richtung | Bi-directional |
| Frequenz | 2400 MHz |
| Konformität | CE compliance (R&TTE directive 1999/5/EC) |
| Bezeichnung | Wireless module |
| Exporthinweis | *The range may be considerably above or below that stated. It is dependent on the environment, antenna technology, transmission power, and the product used. |
| Schnittstelle 1 | RS-232 |
| Schnittstelle 2 | RS-485 |
| Schnittstelle 3 | Configuration interface |
| Kontaktart | PDT |
| Schraubengewinde | M3 |
| E/A-Datenmodus | ≤ 99 (I/O extension modules per wireless network, serial interfaces deactivated) |
| Betriebsart | I/O data (Default setting, configuration via thumbwheel) |
| Statusanzeige | Green LED (supply voltage, PWR) |
| Frequenzbereich | 2.4002 GHz ... 2.4785 GHz |
| Kanalabstand | 1.3 MHz |
| Kontaktmaterial | PdRu, gold-plated |
| Gehäusematerial | PA 6.6-FR |
| Verschmutzungsgrad | 2 |
| Serieller Datenmodus | 0 (no I/O extension modules can be used) |
| Abstreiflänge | 7 mm |
| UL, USA / Kanada | UL 508 Listed |
| Verbindungsmethode | COMBICON plug-in screw terminal block |
| Anzahl der Ausgänge | 1 |
| Anzugsmoment | 0.6 Nm |
| Funklizenzen | Australia |
| Antennenanschluss | RSMA (female) |
| Getriebegeschwindigkeit | 0,3 ... 115,2 kbit/s |
| PLC/Modbus RTU-Modus | ≤ 99 (I/O extension modules per wireless network, access to extension modules via Modbus RTU protocol) |
| Übertragungslänge | ≤ 15 m |
| Schutzgrad | IP20 |
| Überspannungskategorie | II |
| Empfängerempfindlichkeit | -106 dBm (16 kbps) |
| Standardbezeichnung | Ex Directive (ATEX) |
| Versorgungsspannungsbereich | 19.2 V DC ... 30.5 V DC |
| Abschlusswiderstand | 390 Ω (switchable via DIP switches) |
| Montageanleitung | on standard DIN rail NS 35 in accordance with EN 60715 |
| Normen/Vorschriften | EN 60079-0 |
| Vibration (Betrieb) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Spannungsausgangssignal | 0 V ... 3 V |
| Maximaler Schaltstrom | 500 mA (30 V AC/DC) |
| Elektrische Lebensdauer | 5 x 105cycles with 0.5 A @ 30 V DC |
| Maximaler Stromverbrauch | ≤ 65 mA (@ 24 V DC, @ 25°C, stand-alone) |
| Anzahl der Kanalgruppen | 8 |
| Maximale Schaltspannung | 30 V AC/DC |
| Überspannungsschutz | Yes |
| Übertragungskapazität, maximal | ≤ 20 dBm (Outside of Europe, adjustable via software) |
| Mindestübertragungskapazität | 0 dBm |
| Anzahl der unterstützten Geräte | ≤ 250 (Addressing via PSI-CONF software) |
| Anzahl der Kanäle pro Gruppe | 55 |
| Umgebungstemperatur (Betrieb) | -40 °C ... 70 °C (>55°C derating) |
| Leiterquerschnitt AWG max. | 14 |
| Leiterquerschnitt AWG min. | 24 |
| Zulässige Luftfeuchtigkeit (Betrieb) | 20 % ... 85 % |
| Leiterquerschnitt massiv max. | 2.5 mm² |
| Mindestquerschnitt des Leiters (massiv). | 0.2 mm² |
| Anzahl möglicher Erweiterungsmodule | ≤ 32 (per wireless module) |
| Leiterquerschnitt flexibel max. | 2.5 mm² |
| Leiterquerschnitt flexibel min. | 0.2 mm² |
| Brennbarkeitsklasse gemäß UL 94 | V0 |
| Umgebungstemperatur (Lagerung/Transport) | -40 °C ... 85 °C |
| Zulässige Luftfeuchtigkeit (Lagerung/Transport) | 20 % ... 85 % |
Technische Spezifikationen und Leistungsdaten
Installations- und Betriebsanleitung