| Parameter | Wert |
|---|---|
| max. 10 s (Boot time) | |
| Notiz | G3 |
| Tiefe | 113.6 mm |
| Schock | 10g for Δt = 16 ms (continuous shock, 1000 shocks in each space direction) |
| Breite | 22.61 mm |
| Höhe | 107.74 mm |
| Aktuell | max. 30 mA (Sensor current recording per channel) |
| Frequenz | 20 Hz (max. recommended sensor signal frequency, as current input) |
| Präzision | typ. ± 2 % (as current input, relative to the measuring range final value) |
| steckbar | yes |
| Eingabename | IN S1, IN S2, IN S3, IN S4 |
| Schnittstellen | DIN rail TBUS for connection to the master module, supplied as standard |
| Anwendung | Analog IN |
| Beschreibung | Sensor supply voltage per analog input |
| Bezeichnung | A1/A2 |
| Filterzeit | typ. 5 ms (in the event of voltage dips at Us) |
| Produktart | Safety device |
| Neustartzeit | min. 5 s (Boot time) |
| Montageart | DIN rail mounting |
| Ansprechzeit | see user manual |
| Abtastrate | 2.5/5/10/16.6/20/50/60/100/200/400/800/1000/2000/4000 Hz |
| Stoppkategorie | 0 |
| Identifikation | CE-compliant |
| Einschaltstrom | max. 14 A (Δt = 1 ms at Us) |
| Statusanzeige | 4x LED (yellow, red) |
| Versorgungsspannung | 24 V DC ±3 % |
| Gehäusematerial | Polyamide PA non-reinforced |
| Maximale Höhe | ≤ 2000 m (Above sea level) |
| Anzahl der Eingänge | 4 |
| Schutzklasse | III |
| Abstreiflänge | 10 mm |
| Verbindungsmethode | Push-in connection |
| Montageposition | vertical or horizontal |
| Schutzschaltung | Serial protection against polarity reversal |
| Zulässige Spannung | max. 24 V (as current input) |
| Kurzschlussfest | yes |
| Aktuelles Eingangssignal | 0 mA ... 25 mA (Measuring range) |
| Schutzgrad | IP20 |
| Auflösung (aktuell) | 381 nA |
| Auflösung (Spannung) | 152 µV |
| Spannungseingangssignal | 0 V ... 12 V (Measuring range) |
| Montageanleitung | Observe derating |
| Verbindungstechnologie | 2-conductor, 3-conductor or 4-conductor (2-conductor sensor signal + 2-conductor sensor supply) |
| Vibration (Betrieb) | 10 Hz ... 150 Hz, 2g |
| Grenzfrequenz (3 dB) | 160 Hz (RC low pass, 1st order, as current input) |
| Nominaler Betriebsmodus | 100% operating factor |
| Leistungsniveau (PL) | e (2-channel wiring) |
| Stromverbrauch in den USA | typ. 1.96 W (without sensor supply) |
| Auflösung des A/D-Wandlers | 16 bit |
| Beschreibung der Eingabe | Safety-oriented analog inputs, configurable as current or voltage inputs, galvanically isolated |
| Maximal zulässiger Strom | max. 35 mA (as current input) |
| Zulässige Kabellänge | max. 100 m (per input) |
| Bemessungsisolationsspannung | 250 V AC |
| Temperaturkoeffizienten | typ. ± 0.07 %/K |
| Anzeige der Betriebsspannung | 1 x green LED |
| Leiterquerschnitt AWG | 24 ... 16 |
| Sicherheitsintegritätsniveau (SIL) | 3 |
| Leiterquerschnitt starr | 0.2 mm² ... 2.5 mm² |
| Eingangswiderstand Stromeingang | 290 Ω ±25 % (incl. internal protective circuit) |
| Bemessungsstoßspannung/Isolierung | Basic insulation 4 kV between all current paths and housing |
| Umgebungstemperatur (Betrieb) | -10 °C ... 70 °C (observe derating) |
| Bemessungssteuerstrom IS | typ. 82 mA (without sensor supply) |
| Leiterquerschnitt flexibel | 0.2 mm² ... 2.5 mm² |
| Eingangswiderstand der Eingangsspannung | 185 kΩ ±25 % |
| Umgebungstemperatur (Lagerung/Transport) | -20 °C ... 85 °C |
| Bemessungsversorgungsspannung des Steuerkreises (US) | 19.2 V DC ... 28.8 V DC |
| Hinweis zur Verbindungstechnologie | shielded |
| Mindestschutzgrad des Anlagenstandorts | IP54 |
| Maximal zulässige Luftfeuchtigkeit (Lagerung/Transport) | 95 % (non-condensing) |
| Maximal zulässige relative Luftfeuchtigkeit (Betrieb) | 95 % (non-condensing) |
| Maximale Verlustleistung im Nennbetrieb | 2.76 W (with max. permissible load) |
Technische Spezifikationen und Leistungsdaten
Installations- und Betriebsanleitung