| Parameter | Wert |
|---|---|
| • The installation notes/Design In documents online on the download page at phoenixcontact.com/products must be observed for this product. | |
| Notiz | WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201 |
| Tonhöhe | 10 mm |
| Breite [w] | 54.4 mm |
| Höhe [h3] | 43 mm |
| Höhe [h4] | 42.8 mm |
| Länge [l1] | 25.7 mm |
| Länge [l2] | 20.27 mm |
| Sicherheitshinweis | • WARNING: Only electrically qualified personnel may install and operate the product. They must observe the following safety notes. The qualified personnel must be familiar with the basics of electrical engineering. They must be able to recognize and prevent danger. The relevant symbol on the packaging indicates that only personnel familiar with electrical engineering are allowed to install and operate the product. |
| Produktart | Panel feed-through terminal block |
| Spezifikation | IEC 60947-1:2007-06 + A1:2010-12 |
| Produktfamilie | PLW 16 |
| Farbe (Gehäuse) | gray (7042) |
| Artikelüberarbeitung | 03 |
| Steckverbindersystem | PLW 16-6 |
| Kontaktmaterial | Cu alloy |
| Abstreiflänge | 18 mm |
| Verbindungsmethode | Push-lock connection |
| Verpackungsart | packed in cardboard |
| Nennstrom IN | 41 A |
| Nennspannung UN | 1000 V |
| Maßzeichnung | |
| Isoliermaterial | PA |
| Anzahl der Positionen | 3 |
| Anzahl der Potenziale | 2 |
| Nennspannung (II/2) | 1000 V |
| Nennquerschnitt | 16 mm² |
| Anzahl der Verbindungen | 2 |
| Nennspannung (III/2) | 1000 V |
| Nennspannung (III/3) | 1000 V |
| Oberflächeneigenschaften | tin-plated |
| Isoliermaterialgruppe | I |
| Lötstifte pro Potenzial | 1 |
| CTI gemäß IEC 60112 | 600 |
| Bemessungsstoßspannung (II/2) | 6 kV |
| Bemessungsstoßspannung (III/2) | 8 kV |
| Bemessungsstoßspannung (III/3) | 8 kV |
| Leiterquerschnitt starr | 2.5 mm² ... 16 mm² |
| Umgebungstemperatur (Montage) | -5 °C ... 105 °C |
| Umgebungstemperatur (Betrieb) | -40 °C ... 100 °C (Depending on the current carrying capacity/derating curve) |
| Bemessungsisolationsspannung (II/2) | 1000 V |
| Leiterquerschnitt flexibel | 2.5 mm² ... 25 mm² |
| Bemessungsisolationsspannung (III/2) | 1000 V |
| Bemessungsisolationsspannung (III/3) | 1000 V |
| minimale Kriechstrecke (II/2) | 5 mm |
| Mindestkriechstrecke (III/2) | 5 mm |
| Mindestkriechstrecke (III/3) | 12.5 mm |
| Relative Luftfeuchtigkeit (Lagerung/Transport) | 30 % ... 70 % |
| Brennbarkeitsklasse gemäß UL 94 | V0 |
| Umgebungstemperatur (Lagerung/Transport) | -40 °C ... 70 °C |
| Vergleichs-Tracking-Index (IEC 60112) | CTI 600 |
| Mindestabstandswert - inhomogenes Feld (II/2) | 5.5 mm |
| Mindestabstandswert - inhomogenes Feld (III/2) | 8 mm |
| Mindestabstandswert - inhomogenes Feld (III/3) | 8 mm |
| Anschlussrichtung des Leiters zur Steckerrichtung | 0 ° |
| Glühdraht-Entflammbarkeitsindex GWFI gemäß EN 60695-2-12 | 850 |
| Glühdrahtzündtemperatur GWIT nach EN 60695-2-13 | 775 |
| Temperatur für die Kugeldruckprüfung nach EN 60695-10-2 | 125 °C |
| Leiterquerschnitt, flexibel, mit Aderendhülse, mit Kunststoffhülse | 2.5 mm² ... 16 mm² |
| Leiterquerschnitt flexibel, mit Aderendhülse ohne Kunststoffhülse | 2.5 mm² ... 16 mm² |
Technische Spezifikationen und Leistungsdaten