| Parameter | Wert |
|---|---|
| 35 mA (12 V DC) | |
| EMV | A |
| Notiz | When being exposed to interference, there may be minimal deviations. |
| Farbe | gray (RAL 7042) |
| Tiefe | 119.2 mm |
| Breite | 6.2 mm |
| Höhe | 109.81 mm |
| Kommentare | Safety measures must be taken to prevent electrostatic discharge. |
| EMV-Hinweis | EMC: class A product, see manufacturer's declaration in the download area |
| Luftfeuchtigkeit | B |
| Gehäuse | Required protection according to the Rules shall be provided upon installation on board |
| Vibration | A |
| Isolierung | Reinforced insulation according to IEC/EN 61010-1 |
| Zertifikat | CE-compliant |
| Bezeichnung | Electromagnetic RF field |
| Temperatur | B |
| Produktart | Isolating switch transf. |
| Prüfspannung | 3 kV AC (50 Hz, 60 s) |
| Montagehinweis | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. |
| Konfiguration | DIP switches |
| Montageart | DIN rail mounting |
| Identifikation | II 3 G Ex ec IIC T4 Gc |
| Geräuschemission | EN 61000-6-4 |
| Störfestigkeit | EN 61000-6-2 |
| Produktfamilie | MINI Analog Pro |
| Statusanzeige | Green LED (supply voltage) |
| Anzahl der Kanäle | 1 |
| Artikelüberarbeitung | 05 |
| Fehleranzeige | Red LED |
| Gehäusematerial | PBT |
| Leerlaufspannung | 8.2 V DC ±10 % |
| Anzahl der Eingänge | 1 |
| Verschmutzungsgrad | 2 |
| Abstreiflänge | 10 mm |
| Verbindungsmethode | Push-in connection |
| Montageposition | any |
| Stromverbrauch | 450 mW (9.6 V DC) |
| Ausgabebeschreibung | Output 1: Signal output; Output 2: Fault signaling output or signal duplicator, can be set via DIP switches |
| Schaltfrequenz | 5 kHz |
| Schutzgrad | IP20 (not assessed by UL) |
| Elektrische Trennung | 4-way isolation |
| Leitungsfehlererkennung | > 6 mA (Short circuit) |
| Überspannungskategorie | II |
| Versorgungsspannungsbereich | 9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
| Ex-Installation (EPL) | Gc |
| Normen/Vorschriften | EN 61000-4-2 |
| Typische Reaktionszeit | 10 µs |
| Typische Abschaltzeit | 35 µs |
| Kontaktschaltart | 2 N/O contacts |
| Maximaler Einschaltstrom | 50 mA |
| Mindestschaltstrom | 5 mA |
| Nennversorgungsspannung | 24 V DC |
| Verfügbare Eingabequellen | NAMUR proximity sensors (IEC/EN 60947-5-6) |
| Bemessungsisolationsspannung | 300 Vrms |
| Maximale Schaltspannung | 30 V DC |
| Leiterquerschnitt AWG | 24 ... 12 (flexible) |
| Typischer Stromverbrauch | 18 mA (24 V DC) |
| Leiterquerschnitt starr | 0.2 mm² ... 2.5 mm² (with ferrule) |
| Elektromagnetische Verträglichkeit | Conformance with EMC directive |
| Umgebungstemperatur (Betrieb) | -40 °C ... 70 °C |
| Leiterquerschnitt flexibel | 0.14 mm² ... 2.5 mm² |
| Zulässige Luftfeuchtigkeit (Betrieb) | 5 % ... 95 % (non-condensing) |
| Schaltschwellenwert „0“ Signalstrom | < 1.2 mA (blocking) |
| Umgebungstemperatur (Lagerung/Transport) | -40 °C ... 85 °C |
| Schaltschwellenwert „1“ Signal, Strom | > 2.1 mA (conductive) |
| Elektrische Trennung zwischen Eingang und Ausgang | yes |
| Maximale Verlustleistung im Nennbetrieb | 450 mW |
| Brandschutz für Schienenfahrzeuge (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Brandschutz für Schienenfahrzeuge (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Brandschutz für Schienenfahrzeuge (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Technische Spezifikationen und Leistungsdaten
Installations- und Betriebsanleitung