| Parameter | Wert |
|---|---|
| M12 | |
| M18 | 7 mm |
| M30 | 10 mm |
| COM3 | E2EQ-X3B4-IL3 2M |
| Artikel | Model |
| Größe | M12 |
| Baudrate | -IL3: COM3 (230.4 kbps), -IL2: COM2 (38.4 kbps) |
| Materialien | Case |
| Aussehen | Sensing distance |
| Datenlänge | PD size: 2 bytes, OD size: 1 byte (M-sequence type: TYPE_2_2) |
| Indikatoren1 | In the Standard I/O mode (SIO mode): Operation indicator (orange, lit) and stability indicator (green, lit)In the IO-Link mode: Operation indicator (orange, lit) and communication indicator (green, blinking at 1 s intervals) |
| Klemmmuttern | Fluororesin coating (Base material: brass) |
| Abstand einstellen | 0 to 2.4 mm |
| Steuerausgang | Load current |
| Betriebsmodus | PNP NO/NC switching type (Factory setting: NO) |
| Zahnscheibe | Zinc-plated iron |
| Sensoroberfläche | Fluororesin |
| Restspannung | 2 V max. (Load current: 100 mA, Cable length: 2 m) |
| Erfassungsdistanz | 3 mm ±10% |
| Verbindungsmethode | Pre-wired Models (Standard cable length: 2 m), Pre-wired Connector Models (Standard cable length: 0.3 m) |
| Minimale Zykluszeit | -IL3 (COM3): 1 ms, -IL2 (COM2): 2.3 ms |
| Aktueller Verbrauch | 20 mA max. |
| Differenzialübersetzung | 10% max. of sensing distance |
| Antwortfrequenz2 | 1 kHz |
| Schutzgrad | IEC 60529 IP67, in-house standards: oil-resistant |
| Versorgungsspannung | 10 to 30 VDC (including 10% ripple (p-p)) |
| Hauptfunktionen der E/A-Verbindung | Operation mode switching between NO and NC, self diagnosis enabling, excessive proximity judgment distance selecting, timer function of the control output and timer time selecting, instability output (IO-Link mode) ON delay timer time selecting function, monitor output, operating hours read-out, and initial reset |
| Kommunikationsspezifikationen | IO-Link specification |
| M12-Modelle mit vorverdrahtetem Smartclick-Steckverbinder (0,3 m) | 1: +V3: 0 V4: C/Q output |
Technische Spezifikationen und Leistungsdaten
Installations- und Betriebsanleitung