| Parameter | Wert |
|---|---|
| ESM; EMCY | |
| FMMU | 8 |
| Typ | for 3-wire sensors or mechanical switches, PNP, IO-Link Devices |
| PIN 2 | Input/Output (port X0...X7); U-Actuator IO-Link Class B (port X0...X7) |
| PIN 4 | Input/output (port X0...X7); IO-Link master (port X0...X7) |
| IO-Link | 8× Master |
| Feldbus | Ethernet 10/100 Mbit/s; M12, D-coded |
| E/A-Anschlüsse | M12, 5-pole, A-coded |
| Protokolle | CoE; FoE; EoE; AoE |
| Hafenklasse | Class A + B (not galvanically separated) |
| Schutz | IP67 |
| Kabelbruch | per port |
| SYNC-Manager | 4 |
| Spezifikation | IO-Link Master V1.1 |
| Webschnittstelle | yes |
| IIoT-Schnittstellen | yes (OPC UA, MQTT, JSON REST API) |
| Montageart | 2-hole screw mounting, compatible with I/O modules of MVK model range |
| Betriebsarten | COM1; COM2; COM3 (automatic) |
| Aktuatorwarnung | per channel via LED and BUS |
| Sensorversorgung USA | 24 V DC (EN 61131-2), max. 2 A load per port, short-circuit and overload protected, total max. 10 A port X0...X7 |
| Temperaturbereich | -25...+70 °C (storage temperature -40...+80 °C) |
| Aktuatorversorgung UA | 24 V DC (EN 61131-2), max. 10 A Port X0...X7 |
| Diagnose über BUS | per module and channel |
| Diagnose über LED | per module and channel |
| Abmessungen H×B×T | 42×63×225 mm |
| Überwachung – Energie | yes (current and voltage) |
| Übertragungsparameter | 32 Byte (In) 32 Byte (Out) per IO-Link port |
| Kommunikationsstatus | via LED |
| Überwachung – keine Spannung | yes |
| Überwachung - Temperatur | yes |
| Überwachung – Unterspannung | yes |
| Kurzschluss und Überlastung | yes |
| Schaltstrom pro Ausgang | max. 2 A per pin (short-circuit and overload-protected), max. 4 A per port |
| Sensorsystem-/Aktorversorgung | M12 Power, 5-pole, L-coded, 2× max. 16 A |
| Produktartikelnummer des Herstellers | 54612 |